HXGN-12 ring main unit

HXGN-12 box type fixed metal enclosed switchgear (ring main unit) is suitable for use in AC 50Hz, 10kV networks for breaking loads, short circuits, and closing short circuit currents. This ring main unit is equipped with manual and electric spring mechanisms to operate the load switch, while the grounding switch and isolation switch are equipped with manual operating mechanisms. This product complies with standards such as GB3906.

Share
 
 

main technical parameters

Rated voltage 12kV
Rated current 630A
Main busbar current Incoming feeder cabinet 630A
Outgoing feeder cabinet 125A
Rated short-time withstand current 20kA
Rated short-circuit duration 4S
Rated peak withstand current 50kA
Rated Active load breaking current 50kA
Closed loop breaking current 630A
Rated cable charging current 20kA
Rated short-time withstand current of grounding switch 20kA
Rated short-circuit duration of grounding switch 4(2)S
Rated peak withstand current of power switch 50kA
Rated short-circuit closing current of the power switch 50KA
1Min rated power frequency withstand voltage Phase to phase, relative to ground, vacuum load switch fracture 42kV
Lsolation switch fracture 48kV
Rated lightning impulse withstand voltage Phase to phase, relative to ground, vacuum load switch fracture 75kV
Lsolation switch fracture 85kV
Mechanical life Vacuum load switch 10000次
Grounding switch (knife), isolating switch (knife) 20000 Time
Handover current 3150A